Part 5: Equipment-level inspection and operation and maintenance of the fire protection and safety protection system on the energy storage side of the photovoltaic power station

Part 5: Equipment-level inspection and operation and maintenance SOP of the fire protection and safety protection system on the energy storage side of the photovoltaic power station

This article corresponds to the panoramic topology diagram of the energy storage power station [Module 5: Fire Protection and Safety Protection System], covering the heptafluoropropane/aerosol gas fire extinguishing system, nitrogen drive device, combustible gas (CO/H2/VOC) probe, aspirated smoke detector (ASD), fire alarm control panel (FACP), extravehicular emergency shutdown button (EPO), automatic fire linkage cut-off logic and Pack-level water spray backup fire protection system.

1. Gas fire extinguishing system (heptafluoropropane HFC-227ea / aerosol) equipment level maintenance SOP

The gas fire extinguishing system is the first automatic fire-extinguishing barrier when early thermal runaway or open fire occurs inside the battery compartment.

(1) Inspection of fire extinguishing agent gas storage cylinder and driving device

Fire extinguishing agent cylinder pressure and weighing inspection: Check the pressure gauge of the heptafluoropropane (HFC-227ea) gas storage cylinder. In an environment of 20°C, the pointer must be in the green qualified area (2.5 ~ 4.2 MPa). If the pointer drops to the red area, it means that the gas pressure is leaking and must be refilled.

Weighing Test (Annual): Cylinders are weighed and rechecked. When the net weight of the fire-extinguishing agent is reduced by >5% from the initial nominal mass, the cylinder must be removed to replenish the fire-extinguishing agent. Check that the cylinder hoop and anti-vibration rubber gasket are tight and not loose.

Nitrogen-driven small cylinder and solenoid valve (Solenoid Valve): Check the pressure of the nitrogen-driven small cylinder (standard pressure is 6.0 ± 0.2 MPa).

Check the solenoid drive valve electric explosion coil impedance (usually 20 ~ 50 Ω). Check that the mechanical safety pin (Safety Pin) on the solenoid driven valve must be in the released/pull-out standby state to ensure that the solenoid valve can successfully penetrate the cylinder ejector pin during automatic alarm.

(2) Gas fire extinguishing pipe network, selection valve and nozzle

Prevent clogging of nozzles and pipe networks: Check that there are no physical obstructions on the cabin roof and Pack-level gas nozzles, as well as no dust accumulation and oil condensation.

Anti-backflow one-way valve and high-pressure hose: Check that the high-pressure stainless steel metal hose has no cracks or deformation, and the anti-backflow one-way valve is installed in the correct direction and has no trace of leakage.

2. Maintenance SOP for combustible gas detection, smoke/temperature sensor and fire alarm control panel (FACP)

(1) Detector probe calibration and cleaning

All-in-one gas detector: focuses on detecting carbon monoxide (CO), hydrogen (H2), and combustible gas (VOC/methane). The probe indicator light flashes normally (the green light is always on/flashes to indicate normal communication).

Aspirating smoke detector (ASD/VESDA): Check that the air inlet of the aspiration sampling pipe network is not blocked, clean or replace the high-efficiency air filter (HEPA) inside the sampling host; check that the operating current of the air extraction pump and the sampling wind speed are normal.

Smoke and temperature sensing probes: Every six months, use a portable smoke tester and a hot air gun to randomly test the smoke and heat sensitivity of the smoke and temperature sensing probes in the cabin. The response time of the probe must be < 3s, and the main control panel must accurately display the corresponding probe code address.

(2) Fire Alarm Control Panel (FACP - Fire Alarm Control Panel)

Main/backup power automatic switching test: disconnect the FACP main AC power supply (220V AC), and the control panel must seamlessly switch to the backup battery power supply (DC 24V). The backup battery can maintain the control panel's normal monitoring operation time ≥ 24 hours.

Bus communication and shielding self-test: Check that the FACP main screen displays no “fire alarm”, “fault” or “loop shielding” indicator lights.

3. Actual test SOP of extravehicular emergency control panel (EPO) and fire linkage cut-off logic

(1) Extravehicular control panel and manual/automatic switching

Control mode key switch: Check the fire control box next to the hatch. The "manual/automatic" selector switch must be in the "Auto" position all year round.

Emergency stop button (EPO): Check that the mechanical yellow-black protective cover of the red EPO button is intact and not damaged by accidental contact.

(2) Fire safety automatic linkage cut-off logic (millisecond test SOP)

Test cycle: actual measurement using simulated signals once every six months.

Linkage logic and response timing:

Step 1: The fire control panel receives a second-level fire alarm (smoke + temperature sensors are triggered at the same time, or the CO / H2 concentration reaches the deflagration warning line).

Step 2: Start the 30-second audible and visual alarm countdown (to give on-site operation and maintenance personnel time for emergency evacuation, while the outdoor audible and visual alarm will sound wildly).

Step 3: Before the countdown ends (millisecond level), the control panel outputs a dry contact signal to trigger the following three linkage actions:

Action 1: Forcibly cut off the DC main circuit breaker of the battery compartment (trip the BDU/BCU high-voltage contactor and cut off the energy source).

Action 2: Forcibly cut off the power supply to the HVAC air conditioner and the inlet and outlet fans in the cabin to stop the air flow.

Action 3: Close the hatch and air duct fire damper (Damper) to form a confined space.

Step 4: When the countdown is over, start the nitrogen driven valve ➔ Break down the thimble of the heptafluoropropane cylinder ➔ Release the gas fire extinguishing agent ➔ Leave the cabin to suffocate for no less than 20 minutes.

4. Pack-level water sprinkler/submersible backup cooling and fire protection system maintenance

When the battery continues to heat up out of control after the gas fire extinguishing is released, the backup water fire protection system starts to perform powerful cooling.

Fire water inlet pipe and quick-change interface: Check that the standard outdoor fire truck water pump adapter (DN65 or DN80 interface) is free of rust and stuck, and that the rubber dust cover is intact. Check that the antifreeze drain valve of the pipe network is open and drained to prevent water from freezing and cracking the pipes in winter. A 1.0 MPa water pressure withstand test is conducted annually.

Pack-level solenoid water valves and nozzles: Check the insulation resistance of the solenoid water valve coil corresponding to each Pack (≥ 50 MΩ); check that the dust cap (Dust Cap) of the water spray open nozzle is intact.

Photovoltaic power station energy storage side fire protection and safety protection system equipment level inspection on-site inspection sign-in form

Power station name: _______________________________ Inspection date: ____ month ____ day, 2026

Inspection area: Extravehicular fire cylinder area and fire control panel Inspection person in charge: ____________________

1. Field equipment inspection and test data records:

2. Inspection defect registration and defect elimination dispatch:

3. Inspection sign-in and review signature:

Inspection engineer (signature): _______________ Supervision engineer (signature): _______________

Review (signature) of the shift leader: _______________ Sign-in and filing time: ____ hour on ____ month ____ day 2026

第5篇:光伏电站储能侧消防与安全防护系统设备级巡检与运维

第5篇:光伏电站储能侧消防与安全防护系统设备级巡检与运维 SOP

本篇对应储能电站全景拓扑图【模块五:消防与安全防护系统】,涵盖七氟丙烷/气溶胶气体灭火系统、氮气驱动装置、可燃气体(CO/H2/VOC)探头、吸气式烟感(ASD)、火灾报警控制盘(FACP)、舱外紧急停机按扭(EPO)、火灾自动联动切断逻辑及 Pack 级水喷淋后备消防系统。

一、 气体灭火系统(七氟丙烷 HFC-227ea / 气溶胶)设备级维保 SOP

气体灭火系统是电池舱内部发生热失控早期或明火时的第一道自动灭火屏障。

(一)灭火剂储气钢瓶与驱动装置检查

灭火剂钢瓶压力与称重检查:检查七氟丙烷(HFC-227ea)储气钢瓶压力表。在 20 ℃ 环境下,指针必须处于绿色合格区域(2.5 ~ 4.2 MPa)。若指针降至红色区域,说明气体泄压泄漏,必须重新充装。

称重测试(年度):对钢瓶进行称重复核。当灭火剂净重较初始标称质量减少 > 5% 时,必须拆下钢瓶补充灭火剂。检查钢瓶抱箍及防震橡胶垫圈紧固无松动。

氮气驱动小钢瓶与电磁驱动阀(Solenoid Valve):检查氮气驱动小钢瓶压力(标准压力为 6.0 ± 0.2 MPa)。

检查电磁驱动阀电爆线圈阻抗(通常为 20 ~ 50 Ω)。检查电磁驱动阀上的机械安全保险销钉(Safety Pin)必须处于解除/拉出备用状态,确保自动报警时电磁阀能顺利击穿气瓶顶针。

(二)气体灭火管网、选择阀与喷嘴

喷嘴与管网防堵:检查舱顶及 Pack 级气体喷嘴无物理遮挡、无积灰及油污凝结。

防回流单向阀与高压软管:检查高压不锈钢金属软管无龟裂变形,防回流单向阀方向安装正确,无泄漏痕迹。

二、 可燃气体探测、烟感/温感与火灾报警控制盘 (FACP) 维保 SOP

(一)探测器探头校验与清洗

多合一气体探测器:重点检测一氧化碳(CO)、氢气(H2)、可燃气体(VOC/甲烷)探头指示灯闪烁正常(绿灯常亮/闪烁表示通讯正常)。

吸气式烟雾探测器(ASD / VESDA):检查吸气采样管网进气口无堵塞,清洗或更换采样主机内部的高效空气滤芯(HEPA);检查抽气泵运行电流及采样风速正常。

感烟与感温探头:每半年使用便携式发烟测试仪和热风枪对舱内烟感、温感探头进行发烟发热灵敏度抽测,探头响应时间须 < 3s,主控盘须精准显示对应探头编码地址。

(二)火灾报警控制盘(FACP - Fire Alarm Control Panel)

主/备电源自动切换测试:断开 FACP 主交流电源(220V AC),控制盘须无缝切至备用蓄电池供电(DC 24V),备用电池可维持控制盘正常监控运行时间 ≥ 24 小时。

总线通讯与屏蔽自检:检查 FACP 主屏显示无“火警”、“故障”或“回路屏蔽”指示灯。

三、 舱外紧急控制面板 (EPO) 与火灾联动切断逻辑实测 SOP

(一)舱外控制面板与手/自动切换

控制模式钥匙开关:检查舱门旁边的消防控制箱,“手动/自动”选择开关必须常年置于“自动(Auto)”位置。

紧急停机按钮(EPO):检查红色 EPO 按扭的机械黄黑色防护罩完好,无误碰破损。

(二)消防安全自动联动切断逻辑(毫秒级测试 SOP)

测试周期:每半年利用仿真信号实测 1 次。

联动逻辑与响应时序:

第1步:消防控制盘接收到火灾二级告警(烟感 + 温感同时触发,或 CO / H2 浓度达到爆燃预警线)。

第2步:启动 30 秒声光报警倒计时(给现场运维人员紧急撤离的时间,同时舱外声光报警器狂鸣)。

第3步:倒计时结束前(毫秒级),控制盘输出干接点信号触发以下三项联动动作:

动作 1:强行切断电池舱直流总断路器(跳开 BDU / BCU 高压接触器,切断能量源)。

动作 2:强行切断 HVAC 空调及舱内进出风机电源,停止空气流动。

动作 3:闭合舱门及风道防火阀(Damper),形成密闭空间。

第4步:倒计时结束,启动氮气驱动阀 ➔ 击穿七氟丙烷钢瓶顶针 ➔ 释放气体灭火剂 ➔ 舱内静置闷熄不少于 20 分钟。

四、 Pack 级水喷淋 / 浸没式后备降温消防系统维保

当气体灭火释放后电池仍持续热失控升温时,后备水消防系统启动进行强力冷却降温。

消防进水管道与快换接口:检查舱外标准消防车水泵接合器(DN65 或 DN80 接口)无锈蚀死卡,橡胶防尘盖完好。检查管网防冻泄水阀处于打开排空状态,防止冬季积水冻裂管路。每年进行 1.0 MPa 水压耐压测试。

Pack 级电磁水阀与喷头:检查每个 Pack 对应的电磁水阀线圈绝缘阻抗(≥ 50 MΩ);检查水喷淋开式喷头防尘帽(Dust Cap)完好。

光伏电站储能侧消防与安全防护系统设备级巡检现场巡检签到表

电站名称:_______________________________ 巡检日期:2026 年 ____ 月 ____ 日

巡检区域:舱外消防钢瓶区与消防控制盘 巡检负责人:____________________

一、现场设备巡检与测试实测数据记录:

二、 巡检缺陷登记与消缺派工:

三、 巡检签到与复核签字:

巡检工程师(签字):_______________ 监护工程师(签字):_______________

值班长复核(签字):_______________ 签到归档时间:2026 年 ____ 月 ____ 日 ____ 时