This article corresponds to the panoramic topology diagram of the photovoltaic power station [Module 7: Meteorological Monitoring and Intelligent Environmental System]. Meteorological data is the benchmark source for calculating the energy efficiency ratio (PR - Performance Ratio) of the photovoltaic power station, tracking bracket strong wind Stow protection, Anti-PID startup and photovoltaic power prediction system, covering total radiation/incline irradiance meter, louver ambient temperature and humidity meter, patch module board temperature sensor, ultrasonic/mechanical wind speed and direction meter, snow load sensor and MODBUS meteorological data collector.

1. Equipment-level maintenance SOP for total radiation, scattering and slope irradiance meters

Irradiance meters (such as blackbody/photoelectric pyranometers, slope irradiance meters) are used to measure solar radiation intensity (W/m²), and their measurement accuracy directly determines the calculation results of the PR performance ratio of the entire station.

(1) Quartz glass cover cleaning and desiccant discoloration inspection

Glass cover cleaning SOP:

The hemispherical double-layer quartz glass cover on the top of the pyranometer and the inclined surface meter must be kept absolutely clean.

Maintenance requirements: Use a dust-free wipe dipped in absolute ethanol at least once a week to gently wipe dust, bird droppings and scale traces on the surface of the quartz glass cover. Do not scratch the anti-reflective coating on the glass surface when wiping.

Internal desiccant discoloration inspection:

Check the desiccant tank on the lower part of the pyranometer. The color-changing silica gel particles in the tank must be dark blue. If > 2/3 of the silica gel particles are found to turn pink or white, it means that the interior has been saturated with moisture, and the dry silica gel must be replaced immediately to prevent condensation and atomization on the inner wall of the quartz glass cover, resulting in a 5%~15% low irradiance measurement value.

(2) Alignment of level bubble calibration and inclination angle of inclined plane installation

Horizontal bubble calibration: Check the bubble level on the base of the horizontal pyranometer. The bubble in the level bubble must be strictly in the center of the red circle (the level error must be < 0.5°). If the bubble deviates, loosen the base adjustment screw for horizontal calibration.

Angle alignment of the inclined surface irradiance meter: The installation inclination of the inclined surface irradiance meter must be 100% absolutely consistent with the inclination of the photovoltaic array module (the inclination of the fixed bracket or the real-time angle of the flat single-axis tracking bracket) (the inclination angle deviation must be < 0.5°), otherwise it will lead to inaccurate radiation collection and lead to errors in the PR calculation of the entire station.

(3) Sampling error verification and night zero point calibration

Sampling accuracy calibration: Use a standard first-level irradiance meter certified by the national metrology for on-site comparison calibration every year. The sampling error must be ≤ ± 2.0%.

Zero Calibration at night: Check the irradiance data displayed on the SCADA screen in the absence of light at night (theoretical solar irradiance is 0 W/m²). If a small value (such as 2.5 W/m² or -1.8 W/m²) is displayed, "zero offset calibration" must be performed in the background of the weather collector.

2. Maintenance SOP for ambient temperature and humidity meter and component board temperature sensor

(1) Calibration of shutter ambient temperature and humidity meter

Cleaning of radiation-proof louvers: Check that there is no accumulation of dust or clogging of bird's nests in the louvers, and ensure that the louver slots are ventilated smoothly.

Temperature and humidity sensor accuracy verification: Use a measured portable digital temperature and humidity calibrator to compare close to the sensor. The ambient temperature sampling error must be ≤ ± 0.5 ℃, and the relative humidity sampling error must be ≤ ± 3.0% RH.

(2) Maintenance SOP for SMD component board temperature sensor (PT100/PT1000)

The panel temperature of the module directly affects the power output of the photovoltaic cell (usually when the temperature of the crystalline silicon module increases by 1°C, the power decreases by about 0.35%~0.45%), and the panel temperature data is the basis for temperature compensation calculations.

Attachment position and tape inspection:

The board temperature sensor must be closely attached to the center of the backplane of the representative component of the photovoltaic array (avoiding the frame heat dissipation area and junction box).

Check that the 3M thermally conductive high silicone tape and aluminum foil tape are not peeling off or peeling, and there are no air bubbles or gaps to ensure good thermal conductivity between the sensor and the component backplane.

Temperature measurement accuracy verification: When there is sufficient sunlight, use an infrared point temperature gun to measure the temperature of the back plate where the sensor is attached, and compare it with the value displayed on the weather collector. The plate temperature sampling error must be ≤ ± 1.0 ℃.

3. Maintenance SOP for wind speed and direction gauges, sunshine gauges and snow load sensors

(1) Ultrasonic/mechanical wind speed and direction meter maintenance

The wind speed data is directly linked to the strong wind tile (Stow) protection of the tracking bracket, which is a safety-level sensor.

Mechanical wind cup and wind vane: Check that the wind cup and wind vane bearings are well lubricated and rotate without any jamming or abnormal noise. The starting wind speed of the wind cup must be ≤ 0.5 m/s.

Ultrasonic wind speed and direction meter: Check that there is no bird droppings, snow or ice on the surface of the ultrasonic transmitting and receiving probes. When the ambient temperature is < 2°C, the antifreeze heating wire that comes with the ultrasonic anemometer must automatically start to prevent the probe from freezing.

Wind speed sampling accuracy verification: The wind speed sampling error must be ≤ ± 0.3 m/s. The strong wind signal is simulated every six months, and the test weather station sends the strong wind Stow protection broadcast signal to the tracking system normally (response time < 2s).

(2) Rotary sunshine meter and snow load sensor

Photoelectric sensor window of the sunshine meter: Wipe the glass sensor window of the sunshine meter to check that the number of sunshine hours is recorded accurately.

Snow load sensor and snowmelt heating: The installation inclination of the snow load sensor is normal, and the snow load thickness sampling error is ≤ ± 1.0 cm. Check that the anti-snow and freezing heating wire is in good condition.

4. Weather collector, communication bus and data authenticity cross-check SOP

(1) Communication between weather collection box and MODBUS RS485

Collection box protection: The weather collecting box (protection level IP65) door strips are intact, there is no condensation inside the box, and the terminals are not loose or corroded.

RS485 communication bus: The shielding layer of the RS485 communication bus must be grounded at a single point at the collection box end, and the 24-hour communication packet loss rate must be < 0.01%.

(2) SOP for cross-checking the rationality of irradiance and power generation

Set data logic cross-validation rules (Cross-Validation) in the SCADA system background:

Logic rule 1: When the irradiance of the weather station reaches > 200 W/m², but the corresponding inverter output power is 0 kW, the system must report "Inverter does not respond to irradiation power generation abnormality" within < 5s.

Logic rule 2: When the irradiance at night is 0 W/m², but the inverter shows power output, the system must report "abnormal meteorological irradiance zero point deviation".

Photovoltaic power station PV side meteorological monitoring and intelligent environment system equipment level inspection and operation and maintenance sign-in form

Power station name: _______________________________ Inspection date: ____ month ____ day, 2026

Inspection area: Photovoltaic power station meteorological observation station area Inspection person in charge: ____________________

On-site equipment inspection and test measured data records:

2. Registration of inspection defects and dispatch of work to eliminate defects

3. Inspection sign-in and review signature

Inspection Engineer (Signature): _______________ Supervision Engineer (Signature): _______________

Review (signature) of the shift leader: _______________ Sign-in and filing time: ____ hour on ____ month ____ day 2026

第7篇:光伏电站PV侧气象监测与智能环境系统设备级巡检与运维

第7篇:光伏电站PV侧气象监测与智能环境系统设备级巡检与运维 SOP

本篇对应光伏电站全景拓扑图【模块七:气象监测与智能环境系统】,气象数据是光伏电站计算能效比(PR - Performance Ratio)、跟踪支架大风 Stow 保护、Anti-PID 启动及光伏功率预测系统的基准来源,涵盖总辐射/斜面辐照度仪、百叶箱环境温湿度计、贴片式组件板温传感器、超声波/机械风速风向仪、雪载传感器及 MODBUS 气象数据采集器。

一、 总辐射、散射与斜面辐照度仪设备级维保 SOP

辐照度仪(如黑体/光电式总辐射表、斜面辐照度表)用于测量太阳辐射强度(W/m²),其测量精度直接决定全站 PR 性能比计算结果。

(一)石英玻璃罩清洁与干燥剂变色检查

玻璃罩清洁 SOP:

总辐射表及斜面表顶部的半球形双层石英玻璃罩须保持绝对洁净。

维保要求:每周至少使用无尘擦拭布蘸取无水乙醇,轻柔擦拭石英玻璃罩表面的灰尘、鸟粪及水垢痕迹,擦拭时严禁划伤玻璃表面防反射涂层。

内部干燥剂变色检视:

检查辐射表下部的干燥剂罐。罐内变色硅胶颗粒须呈深蓝色。若发现有 > 2/3 的硅胶颗粒变为粉红色或白色,说明内部已吸湿饱和,必须立即更换干燥硅胶,防止石英玻璃罩内壁结露雾化,导致辐照度测量值偏低 5%~15%。

(二)水准泡校准与斜面安装倾角对齐

水平气泡校准:检查水平总辐射表底座上的水准泡(Bubble Level)。水准泡内的气泡必须严格居于红圈中心(水平度误差须 < 0.5°)。若气泡偏离,调松底座调节螺钉进行水平校准。

斜面辐照度仪角度对齐:斜面辐照度仪安装倾角必须与光伏方阵组件倾角(固定支架倾角或平单轴跟踪支架实时角度)100% 绝对一致(倾角偏差须 < 0.5°),否则会导致辐射量采集不准,引发全站 PR 计算错误。

(三)采样误差校验与夜间零点校准

采样精度校准:每年使用经国家计量认证的标准一级辐照度计进行现场比对校准,采样误差须 ≤ ± 2.0%。

夜间零点校准(Zero Calibration):在夜间无光(太阳辐照度理论为 0 W/m²)状态下,检查 SCADA 屏显示的辐照度数据。若显示有微小数值(如 2.5 W/m² 或 -1.8 W/m²),须在气象采集器后台执行“零点偏移校准”。

二、 环境温湿度计与组件板温传感器维保 SOP

(一)百叶箱环境温湿度计校准

防辐射百叶箱清洁:检查百叶箱无尘土堆积、无鸟巢堵塞,保证百叶槽通风顺畅。

温湿度传感器精度校验:使用经过计量的便携式数字温湿度校验仪贴近传感器比对,环境温度采样误差须 ≤ ± 0.5 ℃,相对湿度采样误差须 ≤ ± 3.0% RH。

(二)贴片式组件板温传感器(PT100 / PT1000)维保 SOP

组件板温直接影响光伏电池功率输出(通常晶硅组件温度每升高 1 ℃,功率下降约 0.35%~0.45%),板温数据是温度补偿计算的依据。

贴附位置与胶带检视:

板温传感器须紧密贴附于光伏方阵代表性组件的背板中心位置(避开边框散热区与接线盒)。

检查 3M 导热高硅胶带及铝箔胶带无脱落剥离、无气泡空隙,确保传感器与组件背板热传导良好。

测温精度校验:在阳光充足时,使用红外点温枪实测传感器贴附位置的背板温度,与气象采集器显示值对比,板温采样误差须 ≤ ± 1.0 ℃。

三、 风速风向仪、日照计与雪载传感器维保 SOP

(一)超声波 / 机械风速风向仪检修

风速数据直接联动跟踪支架的大风平铺(Stow)保护,属于安全级传感器。

机械风杯与风向标:检查风杯及风向标轴承润滑良好,旋转无卡阻异响。风杯启动风速须 ≤ 0.5 m/s。

超声波风速风向仪:检查超声波发射与接收探头表面无鸟粪、无积雪冰冻。当环境温度 < 2 ℃ 时,超声波风速仪自带的防冻加热丝须自动启动,防止探头结冰。

风速采样精度校验:风速采样误差须 ≤ ± 0.3 m/s。每半年模拟大风信号,测试气象站向跟踪系统下发大风 Stow 保护广播信号正常(响应时间 < 2s)。

(二)旋转式日照计与雪载传感器

日照计光电感应窗口:擦拭日照计玻璃感应窗口,检查可照时数记录准确。

雪载传感器与融雪加热:雪载传感器安装倾角正常,雪载厚度采样误差 ≤ ± 1.0 cm。检查防雪冻加热丝功能完好。

四、 气象采集器、通讯总线与数据真实性交叉校验 SOP

(一)气象采集箱与 MODBUS RS485 通信

采集箱防护:气象采集箱(防护等级 IP65)门胶条完好,箱内无水汽凝露,接线端子无松动锈蚀。

RS485 通讯总线:RS485 通讯总线屏蔽层须在采集箱端单点接地,24 小时通讯丢包率须 < 0.01%。

(二)辐照度与发电功率合理性交叉校验 SOP

在 SCADA 系统后台设定数据逻辑交叉校验规则(Cross-Validation):

逻辑规则 1:当气象站辐照度达到 > 200 W/m²,但对应逆变器输出功率为 0 kW 时,系统须在 < 5s 内报“逆变器未响应辐照发电异常”。

逻辑规则 2:当夜间辐照度为 0 W/m²,但逆变器显示有功率输出时,系统须报“气象辐照度零点偏移异常”。

光伏电站PV侧气象监测与智能环境系统设备级巡检与运维签到表

电站名称:_______________________________ 巡检日期:2026 年 ____ 月 ____ 日

巡检区域: 光伏电站气象观测站区 巡检负责人:____________________

现场设备巡检与测试实测数据记录:

二、巡检缺陷登记与消缺派工

三、 巡检签到与复核签字

巡检工程师 (签字):_______________ 监护工程师 (签字):_______________

值班长复核 (签字):_______________ 签到归档时间:2026 年 ____ 月 ____ 日 ____ 时